Water-Level Controller

In most houses, water is first stored in an underground tank (UGT) and
from there it is pumped up to the overhead tank (OHT) located on the roof.
People generally switch on the pump when their taps go dry and switch off the pump
when the overhead tank starts overflowing. This results in the unnecessary wastage
and sometimes non-availability of water in the case of emergency.
The simple circuit presented here makes this system automatic, i.e. it
switches on the pump when the water level in the overhead tank goes low and
switches it off as soon as the water level reaches a pre-determined level. It also
prevents ‘dry run’ of the pump in case the level in the underground tank goes below
the suction level.
In the figure, the common probes connecting the underground tank and the
overhead tank to +9V supply are marked ‘C’. The other probe in underground tank,
which is slightly above the ‘dry run’ level, is marked ‘S’. The low-level and high-level
probes in the overhead tank are marked ‘L’ and ‘H’, respectively.
When there is enough water in the underground tank, probes C and S are
connected through water. As a result, transistor T1 gets forward biased and
starts conducting. This, in turn, switches transistor T2 on. Initially, when the
overhead tank is empty, transistors T3 and T5 are in cut-off state and hence pnp
transistors T4 and T6 get forward biased via resistors R5 and R6, respectively.
As all series-connected transistors T2, T4, and T6 are forward biased, they
conduct to energise relay RL1 (which is also connected in series with transistors
T2, T4, and T6). Thus the supply to the pump motor gets completed via the lower
set of relay contacts (assuming that switch S2 is on) and the pump starts filling the
overhead tank.
Once the relay has energised, transistor T6 is bypassed via the upper set
of contacts of the relay. As soon as the water level touches probe L in the overhead
tank, transistor T5 gets forward biased and starts conducting. This, in turn, reverse biases
transistor T6, which then cuts off. But since transistor T6 is bypassed through
the relay contacts, the pump continues to run. The level of water continues to
rise.
When the water level touches probe H, transistor T3 gets
forward biased and starts conducting. This causes reverse
biasing of transistor T4 and it gets cut off. As a result, the relay de-energises and the
pump stops. Transistors T4 and T6 will be turned on again only when the water
level drops below the position of L probe. Presets VR1, VR2, and VR3 are to
be adjusted in such a way that transistors T1, T3, and T5 are turned on when
the water level touches probe pairs C-S, C-H, and C-L, respectively. Resistor R4
ensures that transistor T2 is ‘off’ in the absence of any base voltage. Similarly,
resistors R5 and R6 ensure that transistors T4 and T6 are ‘on’ in the absence of
any base voltage. Switches S1 and S2 can be used to switch on and switch off, respectively,
the pump manually.
You can make and install probes on your own as per the requirement and
facilities available. However, we are describing here how the probes were made
for this prototype.
The author used a piece of nonmetallic conduit pipe (generally used for
domestic wiring) slightly longer than the depth of the overhead tank. The common
wire C goes up to the end of the pipe through the conduit. The wire for probes
L and H goes along with the conduit from the outside and enters the conduit through
two small holes bored into it as shown in Fig. 2.
Care has to be taken to ensure that probes H and L do not touch wire C directly.
Insulation of wires is to be removed from the points shown. The same arrangement can be
followed for the underground tank also. To avoid any false triggering due to interference,
a shielded wire may be used.